Direct-to-chip liquid cooling: a copper cold plate with coolant channels mounted over a GPU package on a PCB, with labels for the TIM, BGA and coolant lines inside an AI server rack

Direct-to-Chip Liquid Cooling in AI Racks: Where the Heat Problem Really Went

How cold plates, clamp loads, coolant chemistry, and quick disconnects became the real engineering constraints inside 130 kW AI racks.

In late 2024, Reuters and others, citing The Information, reported that Blackwell GPUs were overheating in 72-processor servers and that NVIDIA had made multiple revisions to its rack designs. Months later, the Financial Times reported that suppliers had spent several months working through GB200 problems that included overheating and leaks in the liquid-cooling systems. Reuters reported that Jensen Huang had denied earlier media reports that the 72-chip liquid-cooled server was overheating during initial testing.

The technical root causes were never disclosed in enough detail to separate component-level thermal limits from rack-level integration problems. But the reported issues — overheating, coolant leaks, interconnect glitches — show how much besides raw heat-transfer capacity has to work at once in a liquid-cooled rack.

Direct-to-chip liquid cooling didn’t remove the heat problem from AI racks. It moved much of it — out of facility air handling and into a chain of interfaces: coolant, cold plate, thermal interface material (TIM), package, solder, and printed circuit board.

I’ve spent more than 20 years on the PCB manufacturing side of the hardware industry. Much of the industry discussion of liquid cooling is written from the facility side and stops at the rack manifold. The trade-offs that decide reliability sit closer to the board.

How Direct-to-Chip Liquid Cooling Works Inside an AI Rack

Direct-to-chip liquid cooling loop in an AI rack: cold plates, tray hoses, quick disconnects, rack manifold, CDU and facility loop, plus a residual air path
Figure 1. How direct-to-chip liquid cooling moves heat out of a GB300-class rack, and the air path that remains.

A cold plate sits on each major processor package. Coolant runs through each tray, through quick disconnects (QDs) into the rack manifold, and on to a coolant distribution unit (CDU). In HPE’s GB300 NVL72 documentation, the CDU transfers heat from this secondary loop to the facility’s primary loop through a liquid-to-liquid heat exchanger.

Current GB300 Racks Are Hybrid, Not Fully Liquid Cooled

In the GB300 NVL72, the CPUs, GPUs, ConnectX-8 adapters, and NVSwitch components are liquid-cooled, while the OSFP modules, storage drives, and power distribution board components still rely on air. Lenovo lists its configuration as 18 kW air-cooled and 118 kW liquid-cooled, which it describes as about 85% liquid cooled. That remaining load still needs fans and airflow paths. Two thermal regimes share one tray.

Nominal, Peak, and Provisioned Rack Power Are Different Numbers

For its GB300 NVL72 configuration, HPE lists 132 kW nominal TDP and approximately 155 kW peak electrical design power, and recommends provisioning busways for 192 kW.

Bar chart of HPE GB300 NVL72 rack power: 132 kW nominal TDP, about 155 kW peak EDP and 192 kW busway provisioning
Figure 2. Three HPE rack-power figures that answer three different questions.

Collapsing these three into one figure loses the engineering behind each.

Flow Balance Across Parallel Cold Plates

In parallel-fed configurations, cold plates share supply and return manifolds, and flow divides according to each branch’s hydraulic resistance. A cold plate with partial fouling, a kinked hose, or a QD with higher-than-nominal pressure drop gets less coolant than its neighbors.

That failure mode can be quiet. Loop-level supply and return temperatures average across every branch, so a local restriction may be masked in aggregate measurements. Whether it shows up first as a hot device or as a flow alarm depends on the instrumentation, flow monitoring, and control thresholds.

NVIDIA engineers characterized cold-plate thermal and hydraulic behavior using a 1,000 W thermal test vehicle at 0.5–2 lpm and supply temperatures from 17°C to 45°C. They noted that, as of 2023, no standardized methodology existed for testing coolant reliability in these systems.

The Interface Stack: Where Direct-to-Chip Liquid Cooling Risk Concentrates

Direct-to-chip liquid cooling cross-section: heat flows up through the TIM into the cold plate while clamp load flows down through the BGA, PCB and backplate
Figure 3. In direct-to-chip liquid cooling, the heat path and the retention load path run through the same stack (illustrative).

Trace the heat path upward: die (and lid, where the package has one), TIM, cold plate. Now look at the mechanical side. The preload that holds the cold plate against the package is carried by the retention hardware, stiffener, backplate, package, and board together. How much of it becomes stress in the BGA solder joints, or bending in the PCB, depends on the retention architecture: where the load is reacted, how stiff the supports are, and how the parts expand with temperature.

The thermal and mechanical paths are coupled. In my view, that coupling is an under-discussed trade-off in liquid-cooled AI hardware.

TIM Performance Depends on Contact Pressure

A 2006 IEEE study of one phase-change TIM on a bare-die FCBGA package under a heatsink found that application pressure set the bond line thickness, which set thermal performance. The paper’s abstract reports that its statistical model indicated the TIM’s thermal resistance could differ by up to 45% between high- and low-pressure application, and that the pressure effect was more pronounced after reliability stress than immediately after assembly.

This is a study-specific result for one 2006-era material and heatsink assembly, not a prediction for current AI cold plates or TIM chemistries. What it illustrates is qualitative: contact pressure and its uniformity matter.

How Clamp Force Can Reach the BGA and the PCB

A U.S. patent on cooling-structure attachment illustrates the concern. Its background section states that in screw-mounted heatsink designs, the BGA solder joints see elevated pressure along with the thermal interface, and it identifies the BGA as typically the most vulnerable part of the package. That describes one mounting problem, not a universal load path. The actual path has to be evaluated for each assembly.

Depending on the retention architecture, the trade-off looks like this:

  • More clamp force: thinner, more uniform bond line and lower interface resistance, with potentially more package deformation, PCB bending, and solder-joint stress.
  • Less clamp force: lower mechanical stress, but a higher risk of uneven contact, local hot spots, and throttling.
  • Package and board warpage: limits how uniform the contact can be at any force.

JEDEC JESD22-B112C (package warpage measurement at elevated temperature) and IPC-9641 (High Temperature Printed Board Flatness Guideline) address warpage and flatness across the assembly temperature range. They don’t by themselves set operating-temperature deformation or clamp-load limits for a liquid-cooled GPU assembly. Assembly warpage, operating deformation, and mechanical preload are related but different conditions, and each needs its own qualification.

Conceptual chart: interface thermal resistance falls while package, solder and board stress rise as cold-plate clamp load increases
Figure 4. Clamp load has a qualified window, not a “more is better” setting (qualitative).

None of this is new physics. Heatsink retention has been engineered for decades, and the sources cited here establish no controlled comparison showing liquid-cooled racks are less reliable than air-cooled ones. What has changed is scale: large multi-die packages and kilowatt-class loads share one retention design.

My interpretation is that cold-plate retention, backplate design, and PCB stackup and flatness have to be qualified as one system, not as three separately validated parts that meet at integration.

Mounting Holes, Keepouts, and the Power Delivery Network

Cold-plate retention brings its own layout constraints: fastener holes, stiffener and backplate footprints, and component clearances around the package. Mounting holes and their copper clearances can constrain routing and plane continuity near high-current devices, and keepouts can limit how close VRMs sit to the package. The actual impact on power-delivery impedance and current distribution depends on the stackup and has to be evaluated for each board. Either way, the cooling decision shapes the power delivery network before the first layout review.

Going 100% Liquid: What Changes on the PCB

NVIDIA says Rubin is the first of its AI infrastructure generations with 100% liquid cooling at the rack and tray level: every chip and networking component in a closed loop, with fanless compute and switch trays. The company says this required redesigning components that had stayed on air. It says the new trays use a single inlet and outlet and sealed front panels, and that some systems that previously used six rack units now fit in two.

Removing fans means components that relied on forced airflow need new heat paths into the liquid loop. Depending on the component and the mechanical design, those paths can run through thermal pads, spreaders, frames, or shared cold plates. Where one cold plate spans parts of different heights, each with its own tolerance, compliant gap pads of varying thickness are one way to bridge the difference.

Conceptual diagram of a shared cold plate over components of different heights, bridged by gap pads of different thickness
Figure 5. Without fans, assembly tolerance becomes a thermal variable (conceptual).

At a given conductivity and compression, a thicker pad absorbs more tolerance but adds thermal resistance. Tighter height and placement tolerances can raise manufacturing cost and reduce assembly yield. Assembly tolerance becomes a thermal variable. This is engineering inference; NVIDIA has not published Rubin board-level details.

The 45°C Coolant Trade-Off: Facility Efficiency vs. Silicon Margin

At CES 2026, Huang said Vera Rubin would be cooled with 45°C water, and that at that temperature data centers would not need water chillers. NVIDIA says that in its Rubin design, coolant enters at up to 45°C and leaves at roughly 55°C, with processors at full performance. Those are NVIDIA’s stated design conditions, not independent measurements across all installations.

Warm-Water Cooling Has Precedent

In 2012, IBM and the Leibniz Supercomputing Centre announced SuperMUC, described as the first commercially available hot-water-cooled supercomputer, with coolant temperatures up to 45°C. LiquidStack’s CEO noted that Blackwell already used inlet water up to 40°C. ASHRAE TC 9.9’s 5th Edition Thermal Guidelines, published in 2021, already defined W40 and W45 classes.

ASHRAE W17 to W+ liquid cooling classes with Blackwell 40°C and Rubin 45°C inlet temperatures marked
Figure 6. Rubin’s 45°C inlet sits inside ASHRAE’s existing W45 class.

Why Warmer Coolant Spends Silicon Margin

As a first-order, steady-state approximation, junction temperature is the reference coolant temperature plus power multiplied by the effective die-to-coolant thermal resistance. That effective resistance isn’t constant. It shifts with flow rate, the coolant’s temperature rise along the cold plate, heat-flux distribution, and fluid properties.

Still, at the same power and effective resistance, raising the coolant temperature raises the junction by about the same amount.

Warmer water spends silicon temperature margin to buy facility efficiency. Recovering that margin takes a qualified thermal design across the package, TIM, cold plate, and coolant flow. Interface resistance, and with it clamp load, is one of those levers. Without a published thermal-resistance budget for GB300 or Rubin, its share can’t be assumed to dominate.

What “No Chillers” and “Zero Water” Actually Mean

Vertiv’s response was that higher-temperature water does not eliminate heat rejection; the architecture shifts toward liquid-to-liquid transfer or dry coolers. NVIDIA’s “zero water” claim describes its DSX reference design: a dry-cooler-based approach that avoids evaporative cooling water in suitable climates. It is a best-practice guide, not a record of what the industry has built, and it concerns ongoing on-site cooling water, not every use of water in a data center’s life. As Compass Datacenters noted, the fact that Blackwell and Rubin can run at much higher inlet temperatures doesn’t mean they always will, or should.

Coolant Chemistry and Quick Disconnects: Long-Term Reliability Variables

PG25 and Its Alternatives

PG25 — 75% water and 25% propylene glycol — is widely used for direct-to-chip cooling. NVIDIA describes that mix for Rubin, but its own technical documentation says the coolant depends on the customer and data center, with many operators using deionized water or PG25. OCP’s UQD v2.0.0 specification names water and PG25 as test fluids and requires wetted materials to be compatible with water-based and propylene-glycol fluids. A Schneider Electric thermal engineer describes inhibited deionized water as performing well but needing more fluid maintenance, and PG25 as performing nearly as well with far less.

According to the same engineer, the glycol at that concentration inhibits biological growth, and PG25 formulations generally include additional additives to prevent bacterial growth and corrosion in copper components. The inhibitor package, not the glycol alone, carries much of that protection. A University of Texas at Arlington thesis comparing PG-based coolants notes that those additives may come at the expense of thermal performance.

Coolant is a reliability component, not a commodity. Inhibitor depletion, corrosion across the loop’s wetted metals and elastomers, and particulate fouling of fine channels all play out over years. NVIDIA says PG25 can last up to 10 years in a closed loop with minimal maintenance; that is a company claim, not field data. I could not verify representative public data on how they behave across multi-year hyperscale deployments.

OCP UQD Standardization and Leak Risk

The Universal Quick Disconnect (UQD) began as an Intel initiative within OCP and defines interface dimensions so plugs and sockets from different vendors fit together. OCP’s UQD v2.0.0 specification, released in 2026, consolidates the previously separate UQD and blind-mate UQDB specifications into one document.

“Spill-free” has a defined meaning there. The specification sets a maximum fluid loss per disconnect cycle, from 0.02 mL for the smallest size to 0.07 mL for the largest. It also defines tests including seal washout, temperature cycling, and mechanical cycling. That matches the Schneider engineer’s observation that QDs are often slightly wetted on disconnect rather than perfectly dry, one reason PG25 is preferred over ethylene glycol. Danfoss, for one, says it helium-leak tests 100% of its UQD couplings.

Every QD is both a serviceability feature and a potential leak point, which is why rack builders list leak detection as part of the system. Inventec’s Vera Rubin NVL72 rack, for example, includes a leakage detection solution. I could not verify representative, publicly disclosed field-failure rates for QDs, hoses, or cold plates at hyperscale volume.

Liquid-Cooled Busbars: When Coolant Meets Power Delivery

Liquid cooling also reaches the power path. NVIDIA’s MGX rack documentation already describes liquid-cooled busbars and manifolds, with a coolant temperature differential under 15°C at 1,400 A loads. For the Vera Rubin generation, NVIDIA says its third-generation MGX rack uses liquid-cooled busbars supporting up to 5,000 A.

That is a component rating, not a measure of total rack power. Current ratings aren’t comparable across rack designs without the voltage, topology, and continuous or peak condition behind them. The engineering point is simpler: resistive heating scales with the square of current, so busbar thermal design has become part of the coolant loop’s job.

Microfluidics: The Next Step Beyond Cold Plates

Microsoft has tested a different approach: microchannels etched into the back of the silicon so coolant flows directly across the die’s backside. In lab-scale tests, Microsoft reported heat removal up to three times better than cold plates, depending on workload and configuration, and up to a 65% reduction in maximum silicon temperature rise, varying by chip.

Getting there required a package engineered to contain the coolant and an added etching step. Channel depth is its own trade-off: deep enough to avoid clogging, shallow enough to keep the silicon strong.

These are company-reported prototype results, not production capability, and not every future design will go this route. But if microfluidics scales, the package itself becomes part of the fluid system, and qualification responsibility moves upstream to the foundry and the OSAT.

Who Owns the Direct-to-Chip Interface?

The industry has several ways to move more heat. Warmer inlet water and fan-free trays are in announced products. Microsoft’s backside-etched microfluidics is still in the lab. Each brings liquid closer to solder joints, copper planes, and the package itself.

In my assessment, thermal capacity isn’t the only gating question for direct-to-chip liquid cooling in this generation of AI racks, and it may not be the hardest one. The harder question is whether the interfaces are qualified as one system:

  • TIM under clamp load
  • warped packages on large boards
  • parallel flow through fine channels
  • elastomer seals across every QD in the loop
  • inhibitor chemistry in mixed-metal loops

NVIDIA’s rack-scale reference designs centralize much of the specification, and its partner network approves components such as quick disconnects. But a specification isn’t the same as qualification across fabrication, assembly, deployment, and years of field service.

Long-term reliability depends on coordinated system-level qualification and clear ownership of the mechanical, thermal, hydraulic, electrical, and service interfaces. That ownership runs across the chip vendor, the cold-plate supplier, the ODM, the PCB fabricator, and the facility operator. The sources cited here don’t show that this qualification is failing. They show where it now has to happen: at the boundaries between suppliers.


About the Author

Imran Valiani | Sales Director, PCB Electronics Manufacturing

20+ years working with major Bay Area and global tech clients. Founder of Silicon to Software, where I write about the hardware layer — PCB fab, AI gear, autonomous systems, and cyber — the stuff most tech writers have never touched. Literally.

Follow: X @SiToSoftware | LinkedIn

This article was developed with AI assistance and edited, fact-checked, and reviewed by the author. See my full AI disclosure.

Listen to the Silicon to Software podcast on Apple Podcasts, Spotify, or RSS.com — and watch on YouTube.


Sources

Reporting on GB200 / Blackwell rack issues

  1. TrendForce — News report on GB200 rack overheating and order cuts (citing Reuters / The Information)
    TrendForce, 2025.
    https://www.trendforce.com/news/2025/01/14/news-nvidia-gb200-racks-reportedly-overheat-major-clients-cut-orders/
  2. Reuters — “Nvidia’s biggest customers delaying orders of latest AI racks, The Information reports”
    Reuters (republished by The Star), 2025.
    https://thestar.com.my/tech/tech-news/2025/01/13/nvidia039s-biggest-customers-delaying-orders-of-latest-ai-racks-the-information-reports
  3. Tom’s Hardware — “Nvidia GB200 production ramps up after suppliers tackle AI server overheating and liquid cooling leaks” (reporting the Financial Times)
    Tom’s Hardware, 2025.
    https://www.tomshardware.com/tech-industry/artificial-intelligence/nvidia-gb200-production-ramps-up-after-suppliers-tackle-ai-server-overheating-and-liquid-cooling-leaks

NVIDIA and OEM documentation

  1. NVIDIA — Rubin liquid cooling and the DSX AI factory reference design
    NVIDIA Blog, 2026.
    https://blogs.nvidia.com/blog/liquid-cooling-ai-factories/
  2. NVIDIA — “NVIDIA Vera Rubin POD: Seven Chips, Five Rack-Scale Systems, One AI Supercomputer”
    NVIDIA Technical Blog, 2026.
    https://developer.nvidia.com/blog/nvidia-vera-rubin-pod-seven-chips-five-rack-scale-systems-one-ai-supercomputer/
  3. NVIDIA — “Building the Modular Foundation for AI Factories with NVIDIA MGX”
    NVIDIA Technical Blog, 2025.
    https://developer.nvidia.com/blog/building-the-modular-foundation-for-ai-factories-with-nvidia-mgx/
  4. HPE — “NVIDIA GB300 NVL72 by HPE” QuickSpecs
    Hewlett Packard Enterprise, 2026.
    https://www.hpe.com/us/en/collaterals/collateral.a50009244enw.html
  5. Red Hat — “NVIDIA GB300 NVL72” (Ecosystem Catalog hardware listing)
    Red Hat.
    https://catalog.redhat.com/en/hardware/system/detail/312807
  6. Lenovo — “Lenovo NVIDIA GB300 NVL72” 3D tour
    Lenovo Press.
    https://lenovopress.lenovo.com/3dtours/gb300nvl72
  7. Inventec — “Artemis III (NVIDIA Vera Rubin NVL72 Rack)”
    Singapore Technology Week exhibitor listing, 2026.
    https://www.singaporetechnologyweek.com/exhibitor-products/artemis-iii-nvidia-vera-rubin-nvl72-rack

Peer-reviewed research and patents

  1. Shahi, P., Heydari, A., et al. — “Thermal, Hydraulic and Reliability Analysis of Single-Phase Liquid Coolants for Direct-to-Chip Cold Plate Cooling in High-Performance Computing Systems”
    ASME InterPACK 2023, Paper IPACK2023-110576.
    https://par.nsf.gov/servlets/purl/10537461
  2. Bharatham, L., Wong, S. F., Chan, J. L., Chiu, C.-P. — “A Study of Application Pressure on Thermal Interface Material Performance and Reliability on FCBGA Package”
    2006 International Conference on Electronic Materials and Packaging (EMAP), IEEE, 2006. DOI: 10.1109/EMAP.2006.4430584
    https://doi.org/10.1109/EMAP.2006.4430584
  3. Emami, M. — “Characterization of Direct-to-Chip Cold Plates Using Different Fluids at Various Parameters”
    University of Texas at Arlington, Mechanical and Aerospace Engineering Theses, 2024 (master’s thesis, not peer-reviewed journal research).
    https://mavmatrix.uta.edu/mechaerospace_theses/671
  4. U.S. Patent 7,477,527 — “Apparatus for attaching a cooling structure to an integrated circuit”
    USPTO.
    https://image-ppubs.uspto.gov/dirsearch-public/print/downloadPdf/7477527

Standards and specifications

  1. JEDEC — JESD22-B112C, “Package Warpage Measurement of Surface-Mount Integrated Circuits at Elevated Temperature”
    JEDEC Solid State Technology Association (listing via GlobalSpec).
    https://standards.globalspec.com/std/14647106/jesd22-b112c
  2. IPC — IPC-9641, “High Temperature Printed Board Flatness Guideline”
    IPC (listing via DIN Media).
    https://www.dinmedia.de/en/standard/ipc-9641/191815600
  3. ASHRAE TC 9.9 — “Thermal Guidelines for Data Processing Environments, 5th Edition” (reference card)
    ASHRAE.
    https://www.ashrae.org/file%20library/technical%20resources/bookstore/supplemental%20files/therm-gdlns-5th-r-e-refcard.pdf
  4. Open Compute Project — “Universal Quick Disconnect (UQD) Design Specification, Version 2.0.0”
    Open Compute Project, 2026.
    https://www.opencompute.org/wp-content/uploads/2026/10/OCP-Design-Spec_UQD_v2.0.0.pdf
  5. Open Compute Project — “CEJN Universal Quick Disconnect (UQD)” marketplace listing (UQD origin as an Intel initiative)
    Open Compute Project.
    https://www.opencompute.org/marketplace/facilities-physical-infrastructure/cejn-universal-quick-disconnect-uqd/

Manufacturer documentation

  1. Danfoss — “Danfoss Hansen® Universal Quick Disconnect (UQD)” fact sheet
    Danfoss, 2026.
    https://assets.danfoss.com/documents/580741/AI423953312825en-001101.pdf
  2. Schneider Electric (Motivair) — “What coolant should you use for data center liquid cooling? PG25, dielectric fluids, and ASHRAE recommendations”
    Schneider Electric Blog, 2026.
    https://blog.se.com/datacenter/2026/08/14/what-coolant-for-data-center-liquid-cooling-pg25-dielectric-fluids-ashrae-recommendations/
  3. Microsoft — “AI chips are getting hotter. A microfluidics breakthrough goes straight to the silicon to cool up to three times better.”
    Microsoft Source, 2025.
    https://news.microsoft.com/source/features/innovation/microfluidics-liquid-cooling-ai-chips/

Industry reporting and history

  1. Fierce Network — “Supercomputers can stay chill with hot water says Nvidia” (Huang CES 2026 remarks; Vertiv statement)
    Fierce Network, 2026.
    https://fierce-network.com/cloud/nvidia-has-no-chill
  2. Compass Datacenters / The Tech Capital — “What does NVIDIA Rubin really mean for data centre cooling?” (LiquidStack CEO comments)
    Compass Datacenters, 2026.
    https://www.compassdatacenters.com/in-the-news/nvidia-rubin-liquid-cooling-reality-vs-hype/
  3. TechRadar — Report on NVIDIA’s hot-water liquid cooling and the DSX reference design
    TechRadar, 2026.
    https://techradar.com/pro/nvidias-latest-trick-for-cooling-its-data-center-hardware-is-hot-water-hot-liquid-cooling-is-warmer-than-a-hot-tub-but-apparently-does-the-job-pretty-well
  4. TechPowerUp — Report on the LRZ / IBM SuperMUC hot-water-cooled supercomputer announcement
    TechPowerUp, 2012.
    https://techpowerup.com/167860/first-commercial-ibm-hot-water-cooled-supercomputer-to-consume-40-less-energy

Similar Posts

Leave a Reply

Your email address will not be published. Required fields are marked *